Three-phase resonant chokes, 3RTR 7% 440V type

Three-phase resonant chokes, 3RTR 7% 440V type

Purpose and design

Resonant chokes are intended for use in reactive power compensation systems. They are installed in series with the capacitor bank to form a resonant circuit that protects the capacitors from overload. Such an arrangement limits the amplitude of current harmonics and reduces the risk of resonance. Resonant chokes are selected individually for each compensation stage taking into account the rated voltage of the capacitor, its rated power and the required resonant frequency.

Note:
Upon agreement, we can manufacture a non- standard device with the required technical parameters.
The manufacturer reserves the right to make changes to the parameters due to technical product developments.

Technical Standards EN / IEC 60076-6; EN/IEC
Capacitor power
Mains voltage 400 V
Bank rated voltage 440 V
Damping factor [p] 7% (189 Hz)
Frequency 50 Hz
Protection class IP00 or IP23
Insulation class F (1550C)

Wykonanie A
Wykonanie B
Typ Qc In Ln A B C D E F Masa Wykonanie
[kVAr] [A] [mH] [mm] [mm] [mm] [mm] [mm] [mm] [kg]
3RTR-2,5/4407 2,5 3,2 17,25 125 71 110 100 55 5*8 2,4 A
3RTR-5,0/4407 5,0 6,4 8,63 155 77 130 130 57 8*12 3,4 A
3RTR-7,5/4407 7,5 9,6 5,75 155 92 130 130 72 8*12 5,0 A
3RTR-10/4407 10 12,8 4,31 190 82 155 145 58 8*12 6,1 A
3RTR-12,5/4407 12,5 16 3,45 190 92 155 145 68 8*12 7,4 A
3RTR-15/4407 15 19,2 2,88 190 102 155 145 78 8*12 8,7 A
3RTR-20/4407 20 25,6 2,16 210 105 180 165 85 8*12 10,4 A
3RTR-25/4407 25 32,1 1,73 210 115 180 165 95 8*12 12,6 A
3RTR-30/4407 30 38,5 1,44 240 121 205 190 95 11*15 13,3 B
3RTR-40/4407 40 51,3 1,08 240 141 205 190 115 11*15 18,7 B
3RTR-50/4407 50 64,1 0,86 240 151 205 190 125 11*15 22,4 B
3RTR-60/4407 60 77 0,72 240 155 205 190 129 11*15 24,4 B