Single-phase dumping air coils AirECOdTM-7.2 kV

Single-phase dumping air coils AirECOdTM-7.2 kV

Purpose and design

AirECOd type single-phase air coils are designed for use in medium voltage reactive power compensation systems. The purpose of the coils is to limit the initial current that occurs in the circuit when the capacitive compensation stages are switched on. The elements are suitable for indoor use. Externally, the coils are protected with a leakage current-limiting paint to prevent contamination’s transition.

Note:
Upon agreement, we can manufacture a non- standard device with the required technical parameters.
The manufacturer reserves the right to make changes to the parameters due to technical product developments.

Technical Standards EN/IEC 60076-6, EN/IEC
Inductance 0.1 – 0.15 – 0.2 mH
Ratedcurrent 50–75–100–150–200A
Initial current 30 x In
Insulation level Um 7,2 / LI 60 / AC 20 kV
Frequency 50– 60 Hz
Protection class IP 00
Insulation class T50B / F
Ambient temperature -25 ÷ +50 OC
Environment class C1/E0 – indoor